How to deal with electromagnetic interference of ultrasonic level sensor

Publish Time: 2020-03-04     Origin: Site

 At the customer's application site, a two-wire integrated ultrasonic liquid level meter is directly connected to the frequency converter, and the motor speed is controlled by frequency conversion according to the measurement data of the ultrasonic liquid level meter. There is a big error between the measuring data and the actual data. Connecting the ultrasonic liquid level meter to the switch power supply on site, and the measurement will be normal. Connecting it directly to the frequency converter and the echo image will appear. It is caused by the interference of frequency converter.          

 

Step 1: ground the ultrasonic level gauge.       


There are three terminals on the ultrasonic liquid level meter, one of ultrasonic level measurement transducer is specially grounded. After field grounding, the echo pattern becomes as follows.


From the figure, the interference has been reduced a lot, which shows that in the field of electromagnetic interference, grounding is a conventional method to reduce interference. In general, after grounding, it can be measured correctly. However, after the field is grounded, it can not be measured correctly. So it can only be isolated. A signal isolator is added between the on-site frequency converter and the ultrasonic liquid level meter. The signal isolator of ultrasonic level transducer blocks the interference of the frequency converter. The echo menu at this time is as follows:      



At this time, the echo menu is very clear, without any trace of electromagnetic interference. Comparing with the actual liquid level, the ultrasonic level measurement sensor is measured by ultrasonic liquid level meter is correct. Through this example, we know that in case of strong electromagnetic interference sources such as frequency converter, motor, high-voltage wire, etc., we need to do the following steps: First, entering the echo menu (press and hold the up key first, and then press and hold the set key for three seconds, the echo menu will appear. )    


1.Connect the grounding terminal of ultrasonic liquid level meter to the real ground separately, and do not share the same ground with other equipment.    


2.W hen the grounding does not work, a signal isolator shall be installed between the ultrasonic level gauge, PLC, frequency converter and other equipment.  
   
 In the case of solving electromagnetic interference, exit the echo menu (hold down the down key first, and then hold down the set key for three seconds, the echo menu will exit and return to the previous menu. ) 