Non Contact Industrial Ultrasonic Level Sensor for Liquid Level Measurement
Product Description
Non Contact Industrial Ultrasonic Level Sensor for Liquid Level Measurement
Parameters
Technical data |
General Specifications |
Sensing distance 40…450mm(30---350mm) |
Adjustment range 40…450mm(30---350) |
Unusable area 0…40mm(0---30mm) |
Standard target plate 100mm×100mm |
Transducer frequency About 300 kHz |
Response delay About 125ms |
Indicators/Operating means |
LED yellow solid: object in evaluation range flashing: program function |
LED red flashing: fault or program function object not detected |
Electrical specifications |
Operating voltage UB 10…30VDC,ripple10%ss |
No-load supply current ≤20mA |
Output |
Output type 1 switch output E4,NPN NO/NC,programmable |
Resolution 0.11mm at max.sensing range |
Deviation of the characteristic curve ±1% of full-scale value |
Repeat accuracy ±0.1% of full-scale value |
Load impedance >1k Ohm Maximum switching current 200 mA (reverse polarity protection) |
Temperature influence ±1.5% of full-scale value |
Ambient conditions |
Ambient temperature -25…70℃ |
Storage temperature -40…85℃ |
Mechanical specifications |
Protection grade IP67 |
Connection Connector M12x1,4-PIN |
Material Housing brass,nickel-plated |
Transducer epoxy resin/hollow glass sphere mixture; Polyurethane foam |
Weight 60g Compliance with standards and directives |
Standard conformity EN 60947-5-2:2007 Image: |
Dimension:
Adjusting the switching points
The ultrasonic sensor features a switch output with two teachable switching points. These are set by applying the supply voltage - UB or + UB to the TEACH-IN input. The supply voltage must be applied to the TEACH-IN input for at least 1 s.LEDs indicate whether the sensor has recognised the target during the TEACH-IN procedure. Switching point A1 is taught with - UB,A2 with +UB. Five different output functions can be set.
1. Window mode, normally-open function.
2. Window mode, normally-closed function.
3. One switching point,normally-open function
4. One switching point,normally-closed function.
5. Detection of objet presence.
Switching point, Setting distance only after power on. The internal clock can assure can't be changed after 5 mins when power
on. If want to change the switching point, the user can only setting the request distance after power restart.
TEACH-IN window mode,normally-open function -Set target to near switching point -TEACH-IN switching point A1 with - UB -Set target to far switching point -TEACH-IN switching point A2 with + UB | |||
TEACH-IN window mode,normally-closed function -Set target to near switching point -TEACH-IN switching point A2 with + UB -Set target to far switching point -TEACH-IN switching point A1 with - UB | |||
TEACH-IN switching point, normally-open function -Set target to near switching point -TEACH-IN switching point A2 with + UB -Cover sensor with hand or remove all objects from sensing range -TEACH-IN switching point A1 with - UB | |||
TEACH-IN switching point, normally-closed function -Set target to near switching point -TEACH-IN switching point A1 with - UB -Cover sensor with hand or remove all objects from sensing range -TEACH-IN switching point A2 with + UB | |||
TEACH-IN detection of objects presence -Cover sensor with hand or remove all objects from sensing range -TEACH-IN switching point A1 with - UB -TEACH-IN switching point A2 with + UB | |||
Default setting of switching point A1=blind range,A2=nominal distance | |||
LED displays | |||
Displays in dependence on operating mode | Red LED | Yellow LED | |
TEACH-IN switching point Object detected No object detected Object uncertain(TEACH-IN invalid) |
off flashes On |
flashes off off | |
Normal operation | off | Switching state | |
Fault | on | Previous state |
Installation conditions
If the sensor is installed at the environment temperature fall below 0℃,It should do well on the protective measures. In case of direct mounting of the sensor in a through hole using the steel nuts, it has to be fixed at the middle of the housing thread.